Water Dechlorination: Controlling Residual Chlorine

Definition of water dechlorination

Water dechlorination is the reduction or removal of residual chlorine present in the water after a chlorination step. It may be required to protect a downstream process, produce water suitable for industrial use, or reduce chlorine before a release. At Magnor, dechlorination is carried out notably by filtration on activated carbon or by dosing a reducing agent, depending on the application.

Sources of residual chlorine in water

Sources related to treatment and disinfection

Residual chlorine is mainly associated with the use of chlorinated products for oxidation or disinfection. It may remain after contact time and reach a subsequent treatment step or discharge water.

  • Municipal chlorinated water: the residue may need to be removed before certain production processes.
  • Membrane pretreatment: a dechlorination step can protect membranes sensitive to oxidation.
  • Multi-step processing lines: the chlorine used for oxidation may need to be reduced before an ion exchanger, membrane process, or other sensitive step.
  • Discharge water: dechlorination can be integrated before sending the water to a receiving medium.

Some facts about dechlorination

  • In an activated carbon filter, chlorine extraction occurs through a chemical reaction that oxidizes the surface of the carbon.
  • Contact time (EBCT), surface flow, and residual chlorine target are important design parameters.
  • Chemical dechlorination can use reducing salts, including bisulfite, metabisulfite, or thiosulfate, depending on the project requirements.
  • The choice of method depends on water quality, flow rate, residual chlorine target, downstream process, and operating constraints.

Reasons to control residual chlorine in water

  • Protect reverse osmosis membranes and other equipment sensitive to oxidation.
  • Adapt the water to the needs of an industrial or food process.
  • Prevent a chlorine residue from reaching an incompatible treatment step.
  • Meet the project-specific criteria for water discharged into a receiving environment.

Water dechlorination methods

Magnor selects the dechlorination method based on the water to be treated and the desired result. The documented solutions include:

  • Granular activated carbon (CAG) filtration: reaction of chlorine with the surface of the carbon; design according to flow, surface flow, and EBCT; possibility to integrate filters in parallel and redundancy as needed.
  • Dosage of a reducing agent: controlled injection of bisulfite, metabisulfite, or thiosulfate to neutralize residual chlorine; dosage, mixing, and monitoring must be defined for each application.
  • Instrumentation and automation: residual chlorine analysis, alarms, and control logic to confirm performance and protect downstream equipment.

Turnkey water dechlorination solutions

Each dechlorination application has specific constraints. Magnor can design and provide an integrated solution including activated carbon filters, chemical injection units, instrumentation, control panels, and required auxiliary equipment. Magnor's facilities use dechlorination for process water, downstream equipment protection, and wastewater treatment.

How can Magnor help you?

Magnor can design and provide an integrated solution including activated carbon filters, chemical injection units, instrumentation, control panels, and required auxiliary equipment.


FAQ

It is the reduction or elimination of residual chlorine present in the water after a chlorination step. It may be required to protect a downstream process, produce water suitable for industrial use, or reduce chlorine before a release.

Residual chlorine is mainly associated with the use of chlorinated products for oxidation or disinfection. It is notably found in chlorinated municipal water and in treatment lines where chlorine acts as an oxidant.

To protect reverse osmosis membranes and other equipment sensitive to oxidation, adapt the water to the needs of an industrial or food process and meet project-specific criteria for water discharged into a receiving environment.

The two main methods are filtration on granular activated carbon (CAG), where chlorine is removed by a chemical reaction with the surface of the coal, and the assay of a reducing agent such as bisulfite, metabisulfite, or thiosulfate. Instrumentation to monitor residual chlorine then confirms performance.

Contact time (EBCT), surface flow, and residual chlorine target are important design parameters.